REDFIELD 2011

Redfield Estates           EPA # 0612080
Inorganic Contaminants Date(s) Collected Highest Detect Range Detected MCL or MRDL MCLG or MRDLG Violation Yes/No Typical Source of Contaminant
Sodium (ppm) 11/12/09 16.8 N/A Not Regulated N/A Natural sources; runoff from use as salt on roadways; by-product of treatment process
Volatile Organic Contaminants              
Chlorine (ppm) 2010 0.47 Avg 0.3 - 0.75 4 4 No Water additive used to control microbes
Total Trihalomethanes (ppb) 8/9/10 10 N/A 80 0 No By-product of drinking water chlorination
Haloacetic Acids (ppb) 8/9/10 1.4 N/A 60 0 No By-product of drinking water chlorination
Radiological Contaminants              
Compliance Gross Alpha (pCi/L) 2005 4.3 nd - 4.3 15 0 No Erosion of natural deposits
Radium 226 & 228 (pCi/L) 2005 1.4 0.5 - 1.4 5 0 No Erosion of natural deposits
Uranium (ppb) 2005 7.3 4.0 - 7.3 30 0 No Erosion of natural deposits
Radon (pCi/L) 4/5/10 2,910 N/A Not Regulated N/A Erosion of natural deposits
  Date(s) Collected 90th Percentile Action Level MCLG # of Sites Sampled # Sites Above Action Level Violation Yes/No Typical Source of Contaminant
Lead (ppb) 4/15/09 7 15 0 5 0 No Corrosion of household plumbing system
Copper (ppm) 4/15/09 0.370 1.3 1.3 5 0 No Corrosion of household plumbing system
What is the source of my drinking water?
The sources of the Redfield Estates water supply include two wells located near the lower pump station off Redfield Circle in East Derry, NH.  Well # 1 is located 10 feet north of the pump house and well # 4 is located 1,000 feet southeast of the pump house.  Additional sources are six wells located in the Drew Wood system off Olsen Rd. near Drew Woods Dr. in East Derry, NH.  Treatment consists of chlorine addition to kill bacteria and phosphate addition to sequester iron and mangannese and provide corrosion control.
Text Box: On 7/6 and 7/7 of 2010 approximately 18,000 gallons of drinking water was transferred each day from Pennichuck Water Work's Treatment Plant in Nashua to the Redfield storage tank.  This was done because the storage tank was low due to over use and interruption of the Drew Woods interconnection.
Source Water Assessment Summary
    Summary of Susceptibility Factors
Source Name Date Low Med High
Bedrock Well # 1 9/17/01 9 2 1
Bedrock Well # 4 9/17/01 10 1 1
The complete Assessment Report is available for review.  For more information call Gary Tetley at 800-553-5191 ext. 2378 or visit NH Department of Environmental Services Drinking Water and Groundwater Bureau web site at http://www.des.nh.gov/organization/divisions/water/dwgb/dwspp/reports/index.htm