| Autumn Woods | EPA # 2052070 | |||||||||
| Inorganic Contaminants | Date Collected | Highest Detect | Range Detected | MCL or MRDL | MCLG or MRDLG | Violation Yes/No | Typical Source of Contaminant | |||
| Arsenic (ppb) | 7/13/10 7/28/10 | 11 | nd - 11 | 10 | N/A | No | Erosion of natural deposits; runoff from orchards; runoff from glass and electronics production wastes. | |||
| Barium (ppm) | 7/13/10 7/28/10 | 0.031 | nd - 0.031 | 2 | 2 | No | Erosion of natural deposits; discharge from metal refineries | |||
| Cadmium (ppb) | 7/13/10 7/28/10 | 2 | nd - 2 | 5 | 5 | No | Corrosion of galvanized pipes; erosion of natural deposits; discharge from metal refineries; runoff from waste batteries and paints | |||
| Fluoride (ppm) | 7/13/10 7/28/10 | 0.24 | 0.23 - 0.24 | 4 | 4 | No | Erosion of natural deposits | |||
| Sodium (ppm) | 8/2/07 9/22/08 | 11 | 7.5 - 11 | Not Regulated | N/A | Natural sources; runoff from use as salt on roadways; by-product of treatment process | ||||
| Volatile Organic Contaminants | ||||||||||
| Chlorine (ppm) | 2010 | 0.48 Avg | 0.1 - 0.8 | 4 | 4 | No | Water additive used to control microbes | |||
| Total Trihalomethanes (ppb) | 8/10/10 | 20.0 | N/A | 80 | 0 | No | By-product of drinking water chlorination | |||
| Haloacetic Acids (ppb) | 8/10/10 | 6.5 | N/A | 60 | 0 | No | By-product of drinking water chlorination | |||
| Radiological Contaminants | ||||||||||
| Compliance Gross Alpha (pCi/L) | 2009 | 36 | nd - 36 | 15 | 0 | No | Erosion of natural deposits | |||
| Uranium (ppb) | 2009 | 5.9 | 0.4 - 5.9 | 30 | 0 | No | Erosion of natural deposits | |||
| Radium 226 & 228 (pCi/L) | 2009 | 3.4 | nd - 3.4 | 5 | 0 | No | Erosion of natural deposits | |||
| Radon | 5/11/10 | 1,210 | N/A | Not Regulated | N/A | Erosion of natural deposits | ||||
| Date Collected | 90th Percentile | Action Level | MCLG | # of Sites Sampled | # Sites Above Action Level | Violation Yes/No | Typical Source of Contaminant | |||
| Lead (ppb) | 5/22/08 | < 5 | 15 | 0 | 5 | 0 | No | Corrosion of household plumbing system | ||
| Copper (ppm) | 5/22/08 | 0.781 | 1.3 | 1.3 | 5 | 1 | No | Corrosion of household plumbing system | ||
| What is the source of my drinking water? | ||||||||||
| The sources of the Autumn Woods water supply is three wells located off Route 111 in North Salem, NH. Well #1 is located 175' north of the pump house, well # 3 is located 91' north of the pump house, and well # 4 is located 1,160' northeast of the pump house. Treatment consists of chlorine for disinfection and filtration to remove iron and manganese. An aeration device is used to remove radon from the water. | ||||||||||
| Source Water Assessment Summary | ||||||||||
| Summary of Susceptibility Factors | ||||||||||
| Source Name | Date | Low | Med | High | ||||||
| Bed Rock Well # 1 - 001 | 12/30/02 | 8 | 3 | 1 | ||||||
| Bed Rock Well # 3 - 002 | 12/30/02 | 9 | 2 | 1 | ||||||
| Bed Rock Well # 4 - 003 | 12/30/02 | 9 | 2 | 1 | ||||||
| The complete Assessment Report is available for review. For more information call Gary Tetley at 800-553-5191 ext. 2378 or visit NH Department of Environmental Services Drinking Water and Groundwater Bureau web site at http://www.des.nh.gov/organization/divisions/water/dwgb/dwspp/reports/index.htm | ||||||||||